Fire Alarm System Device Inspection and Maintenance

Fire Alarm System Device Inspection and Maintenance

Views : 2470
Author : ASENWARE
Update time : 2023-07-05 13:36:49
Building fire safety is important for people’s lives. Therefore, installing fire protection facilities in strict accordance with fire protection technical specifications and carrying out regular maintenance is significant.

Linear beam smoke detector

Inspection requirements:

1. Check whether the linear beam smoke detector works properly every quarter.

2. There should be 10% spare parts for linear beam smoke detectors.

 

Maintenance:

1. Re-tighten the loosely connected terminals of the equipment, replace the wiring parts such as screws with rust marks, terminal gaskets, etc., remove the rusted wire ends, and reconnect after tinning.

2. Clean the optical window with special cleaning tools or soft cloth and appropriate detergent every quarter. After cleaning, calibrate the detector response threshold to the threshold set by the factory.

3. Necessary functional tests should be done after the linear beam smoke detector is cleaned, and it can continue to be used only after passing the test.

 


Aspirating smoke detector

Inspection requirements:

1. Check whether the working status of the aspirating smoke detector is normal every quarter.

2. Check the event record of the aspirating smoke detector every quarter to understand the situation of the protected area.

3. Check the status and usage of the filter of the aspirating smoke detector every quarter, and judge whether the filter needs to be replaced.

4. Check the airflow value displayed on the aspirating smoke detector quarterly. Judging the blockage of the sampling pipeline and dealing with the problem in time.

5. Check the sampling pipeline every six months for blockage, rupture, loose fixation, etc., and deal with problems in time.

 

Maintenance:

1. Re-tighten the loosely connected terminals of the equipment, replace the wiring parts such as screws with rust marks, terminal gaskets, etc., remove the rusted wire ends, and reconnect after tinning.

2. For the aspirating smoke detectors that sample through the sampling pipe, flush the sampling pipe at least once a year, replace the filter once a year, and conduct an alarm function test.

3. Maintain according to the equipment product manual.

 


Point-type flame detector

Inspection requirements:

Check whether the point-type flame detector works normally or not every quarter.

 

Maintenance:

1. Re-tighten the loosely connected terminals of the equipment, replace the wiring parts such as screws with rust marks, terminal gaskets, etc., remove the rusted wire ends, and reconnect after tinning.

2. Maintain according to the product manual.

3. Use special cleaning tools or soft cloth and appropriate detergent to clean the optical window.

 


Manual call point

Inspection requirements:

1. Check every quarter whether the working status of the manual call point is normal.

2. Check the functions of the button alarm contacts of the manual call point and the mechanical alarm parts every quarter.

 

Maintenance:

1. Re-tighten the equipment, connect loose terminals, replace wiring components such as screws with rust marks, terminal gaskets, etc., remove the rusted wire ends, and reconnect after tinning.

2. Solve the component fault problems to ensure the operation and normal functions of the device.

 


Strobe sounder

Inspection requirements:

Check if the strobe sounder works normally every quarter.

 

Maintenance:

1. Re-tighten the loosely connected terminals of the equipment, replace the wiring components such as screws with rust marks, terminal gaskets, etc., remove the rusted wire ends, and reconnect after tinning.

2. Use special cleaning tools or soft cloth and appropriate detergent to clean the surface stains of strobe sounders.
Related News
Read More >>
The floods are merciless, Asenware has love - fighting floods with Bangladesh The floods are merciless, Asenware has love - fighting floods with Bangladesh
Sep .12.2024
Flood merciless, but there is love in the world. When Asenware knew Bangladesh was in the midst of a flood disaster, On September 6th, Asenware, with the support of local partners, Four different Bangladeshi charities: As-Sunnah Foundation, trustful trading LTD, Bangladesh Red Crescent Society, Chief Advisor's Relief and Welfare Fund are donated by Asenware,
What is Fire Hose? What is Fire Hose?
Oct .13.2023
A fire hose is a highly pressurized hose that is used to bring water to the fire. It may also transport flame retardants. Fire hoses can be attached to either a fire engine or a fire hydrant, and the pressure is between 800 and 2000 kPa. For reasons of fire safety, it's quite important to have a fire hose inspection as well as all fire protection equipment tested.  If, during a fire emergency, the fire hose fails it could have disastrous results.
What is Water-proof Fire Alarm System? What is Water-proof Fire Alarm System?
Sep .15.2023
Waterproof Heat Detector
Fixed Temperature Waterproof Heat Detector, the detector uses a bi-metallic strip to sense temperature change, therefore consuming minimal standby current and providing high reliability.
The Detector is particularly suited to environments, which are exposed to high levels of condensation or are hosed down. The detector has a wide operating margin allowing it to respond to both slow and fast increases in temperature; it can also sense temperature reliably in a horizontal or vertical position.
Addressable Explosion-proof Fire Alarm System Introduction Addressable Explosion-proof Fire Alarm System Introduction
Aug .08.2023
The Explosion Proof range of products has been designed to provide protection against explosions and products to ensure that all major advantages of high-quality fire detection technology can be safely exploited in industrial and hazardous environments. Many difficult sites such as metal, paint, pipelines, chemical, pharmaceutical, oil refineries, and other installations are vulnerable to the risk of explosion. In order to protect the assets and people, they need special solutions for fast and reliable fire detection.